The Surgistor Series Surge Protection System
Cat. #SURG20
Price $116.00
Distinctive Features
- Complete electrical symmetry simplifies installation
- Equal performance for surges of either polarity
- Greater than 60,000 Amp surge capability
- Instantaneous response to surges
- Double sealed construction for harsh environments
- Long life with M. C. Miller Co., Inc. dependability
Application
The Surgistor
Series of surge protectors are designed for use on AC or DC
systems. Primary applications would be the protection of
sensitive electronic equipment used in the remote monitoring
or interruption of rectifier systems and the protection of the
rectifier itself. The protector is designed for connection to
the anode/cathode terminals and ground, and to the AC mains
and ground. Two Surge Arrestors offer affordable protection to
both the input and output of a rectifier system.
Method of Operation
When a surge or transient exceeds the operational voltage of the Surge Arrestor, the
surge is bypassed to ground. This protection continues until the surge voltage
reduces below the threshold of the Surge Arrestor. The protection system
resumes normal operation after the surge passes without interrupting
either the input or output power. The symmetrical design of the
Surge Arrestor clamps surges equally between any two leads. This maintains all potentials
to a safe level.
Installation
Installation has been eased by the symmetrical construction of the Surge Arrestor. The
technician doing the installation only needs to connect the three
wires of the Surge Arrestor to the appropriate terminals.
For the most effective use, the wire lengths of the Surge Arrestor should
be trimmed as short as is reasonable for the installation.
In other words, there should be no excess wire!
Do not coil excess wire, remove it.
Coiled wire acts as an inductor and lowers the effective clamping
action of the Surge Arrestor. Before installation, determine a suitable
location for placement of the Surge Arrestor within the system to be
protected. This position should not be subject to temperatures in
excess of 65oC. A standard one-inch threaded fitting with
nut is provided as a means of mounting, if desirable. The best
position in the one that requires the least lead length.
Anode/Cathode, Ground Connection
Observe rectifier current before turning off, then turn off. With the rectifier
turned off and the Surge Arrestor placed in what has been determined as a
suitable position, take one of the three leads and bring it over to
the ground connection. Allow about two to three inches of slack in
the wire and cut the remainder off. Trim the insulation back about
one-half inch, select a crimp connector and crimp.
Bolt the wire to the ground clamp. repeat this procedure for the
Anode and then the Cathode connection. Turn power on and observe
that the rectifier current is the same. If the current is not the
same turn off power immediately and check all connections. Turn
power on again. If the current is too high, remove the
Anode/Cathode connection and try again. If the current returns to
normal, the Surge Arrestor may be defective, return it for a
replacement. If the current remains high after removal of Anode and
Cathode connections, check for other causes. Reinstall the
Anode/Cathode connections after determining the problem. Check
system current once again.
AC Mains, Ground Connection
Turn off the AC power to the rectifier. Following the connection procedure outlined in
the Anode/Cathode Ground Connection, connect ground, Hot and
Neutral. Verify connections are tight and no shorts are present.
Turn on AC power. Wait about one minute then feel the Surge Arrestor. If the Surge Arrestor feels warm,
remove it and return it to M. C. Miller Co., Inc. as it may be defective.
| Electrical Specifications |
| |
SURG20 |
| Clamp Voltage: |
275VAC; 275VDC |
| Surge Current: |
64,000 Amps (8/20µS wave) |
| Energy Absorption: |
1208 Joule (Watt Seconds) |
| Tolerance: |
+/- 10% |
| Temperature: |
-40oC to +75oC |
| Physical Specifications |
| |
SURG20 |
| Height: |
3.5" |
| Diameter: |
3.75" |
| Weight: |
8.0 oz. |
| Wire: |
3 feet each X 3, 10 gauge stranded, 600V insulation |
Hermetically sealed construction can withstand indefinite immersion in water.
All units supplied with mounting hardware and crimp connectors.